Transformer Impedance Short-Circuit Assessor

Calculate potential secondary short-circuit fault current ($I_{sc}$) based on transformer kVA and percent impedance ($\%Z$).

Short-Circuit Fault Equations: I_FLA = (kVA × 1000) / (1.732 × V_sec) | I_sc = I_FLA / (%Z / 100)

Transformer Parameters

Typical dry-type values: 2.0% to 5.75%
Full Load Current ($I_{FLA}$) 208.2 A
Max Fault Current ($I_{sc}$) 8,328 A
Recommended AIC Rating 10 kAIC

Electrical System Single-Line Parameter Diagram

PRIMARY SIDE: Inrush Current Factor ~ 10x - 12x FLA
Transformer Rating: 75 kVA | Impedance: 2.5% Z
SECONDARY BUS FAULT POINT: Maximum Available Peak Short-Circuit = 8,328 Amps

Route Transformer System Specifications